Search
JUNXY-TA Battery Monitoring System
Cell Check Intelligent Battery Monitor Testing:
Internal Resistance, Voltage and Temperature Measurements

JUNXY-TA CELLCHECK Intelligent Battery Monitoring System 

---Internal Resistance, Voltage and Temperature Measurements


Overview

JUNXY-TA intelligent battery monitoring system is designed specifically for single cell. It combines the advanced technology with patented for the most thorough stationary battery health analysis in the industries of UPS, telecommunications, battery supplied applications, utilities, fire & safety system, remote monitoring and many more.

 

--Continuous 24/7 on-line monitoring

--Each CELLCHECK tests only one cell, monitoring internal resistance, voltage and temperature

--Software is available to collect data from CELLCHECK

--Serial port with Optical isolation, meet MODBUS protocol, easy to be accessed by UPS controller

--Easy to install without specialized training

 

Features

--Full resistance, battery temperature and voltage monitoring for comprehensive battery state of health analysis

--String current and ambient temperature monitoring(need TC module)

--Automatic analysis of battery monitoring data, find out the batteries that need replacement or maintenance (need CM module)

--With a big storage space to save history data

--Lights on panel flash when alarms rise up which also can be read over through serial bus

--All operating parameters can be set over through serial bus

--A software base on PC is available to manage multiple strings, check real-time alarm and historical data

 

Technical Specifications

Model

JUNXY-TA CELLCHECK Battery Monitoring System

Environment

Operating temperature: -5℃~50℃,5%~90%RH

Storage temperature: -10℃~70℃,5%~90%RH

For Battery

2V, 6V or 12V battery, capacity less than 2000AH

 

Power Requirement

CELLCHECK: powered from the battery,less than 60mA(2V) or 25mA(12V)

TC module: DC8~13V, 2W

Convertor: DC8~13V, 0.3W

CM module: 85~264VAC, 100V~370VDC, 15W

Protection

Test load and power paths are fused

 

 

Measurement

Range & Accuracy

String voltage: 20~800V,±(0.5%+0.2V)

Cell voltage: 1.5~2.5V,±(0.1%+1mV)

            9~15V,±(0.1%+10mV)

Internal resistance: 100~65535uΩ

Battery temperature: 5℃~50℃, ±1.5℃

Ambient temperature: -10℃~+70℃,±0.5℃

String current: 0~500A, ±2%(Full scale)

 

Communications Interfaces

CELLCHECK: serial port, meet MODBUS protocol, support 130 devices on each bus

TC module: serial port, meet MODBUS protocol

CM module: RS485, Ethernet Port, meet MODBUS/RTU, MODBUS/TCP and SNMP protocol

Insulation

2000VAC

Installation

Paste on battery or rail mounting

Weight

CELLCHECK: 115g    TC module: 260g

CM module: 1.8Kg


Options

--Converter--Used for the applications without CM module and connecter to a controller directly.

--Software--It can be installed on PC and read and display data from CM module